Get a quote

10 kVA Online UPS

N Series 6/10 kVA Online UPS -10 kVA Online UPS

Delta Amplon N Series

6 kVA & 10 kVA Online UPS for Critical Power Protection

The Delta Amplon N Series 6 kVA and 10 kVA Online UPS provides reliable single-phase power protection for servers, networking equipment, POS systems, ATMs, office infrastructure and mission-critical commercial applications.

Built on true online double-conversion technology, the N Series delivers zero transfer time, unity output power factor and efficient power conditioning to protect sensitive equipment from outages, voltage fluctuations and electrical disturbances.

  • 6 kVA / 6 kW & 10 kVA / 10 kW
  • True online double conversion
  • Unity output power factor
  • Up to 95% AC-AC efficiency
  • Up to 98% ECO mode efficiency
  • Parallel redundancy up to 4 units
6 & 10 kVA 6 kW and 10 kW usable output
Power Factor 1.0 Maximum usable UPS capacity
Up to 95% AC-to-AC operating efficiency
Up to 4 Units Parallel expansion and N+X redundancy
Available Capacities

Choose Between 6 kVA and 10 kVA Online UPS

The correct UPS capacity depends on connected load, required backup duration, equipment type, starting load and future power requirements.

6 kVA / 6 kW

6 kVA Online UPS

A compact single-phase online UPS for server racks, workstations, networking equipment, POS systems, office infrastructure and critical electronic loads.

N-6K Single Phase Online UPS
10 kVA / 10 kW

10 kVA Online UPS

Designed for higher critical loads including small server rooms, IT infrastructure, ATMs, commercial equipment and production systems requiring dependable continuous power.

N-10K 10 kW Output Parallel Ready

Need help selecting 6 kVA or 10 kVA?

Share your connected load and required backup time. MPower can recommend the suitable UPS and battery configuration for your application.

Get Recommendation
Key Features

High-Performance 10 kVA Online UPS Technology

The Amplon N Series combines compact construction, high efficiency and advanced power protection for business-critical applications.

01

True Online Double Conversion

The UPS continuously conditions incoming power and supplies stable pure sine wave output to connected equipment.

02

Zero Transfer Time

During a mains power failure, connected critical equipment continues operating without transfer interruption.

03

Unity Output Power Factor

The 6 kVA model delivers up to 6 kW and the 10 kVA model delivers up to 10 kW, maximizing available UPS capacity.

04

High Energy Efficiency

AC-to-AC efficiency reaches up to 95%, while ECO mode efficiency reaches up to 98% to help reduce operating losses.

05

N+X Parallel Redundancy

Up to four compatible UPS units can operate in parallel for capacity expansion and improved power-system redundancy.

06

Advanced DSP Control

Digital Signal Processor control provides rapid processing, simplified control architecture and enhanced system stability.

07

Generator Compatible

Generator compatibility helps maintain reliable power protection during prolonged mains outages and generator operation.

08

Intelligent Battery Management

Intelligent charging and battery management help optimize battery performance, reliability and service life.

09

Variable Fan Speed Control

Multi-stage automatic fan regulation helps reduce audible noise, improve efficiency and extend fan service life.

10

Flexible UPS Monitoring

LCD, LED indicators, RS-232, USB, REPO, parallel ports and a Smart Slot provide convenient local and remote management options.

Compact & Efficient

Designed to Reduce UPS Space and Operating Cost

The Amplon N Series is engineered to provide high usable power from a compact footprint, making it suitable for installations where equipment-room space and energy efficiency are important.

A

Compact Footprint

Dimensions of approximately 190 × 390 × 325 mm help conserve valuable space for servers, networking equipment and other critical infrastructure.

B

Lower Power Losses

High operating efficiency can reduce wasted energy, cooling requirements and long-term electricity costs.

C

Reduced Battery Usage

A wide input operating range allows the UPS to tolerate varying utility conditions without unnecessarily switching to battery power.

D

Scalable Protection

Parallel capability allows businesses to expand protected capacity or implement redundancy as operational requirements grow.

Suitable Applications

Where 6 kVA and 10 kVA Online UPS Systems Are Used

The N Series is suitable for commercial, IT, banking, telecom and production environments requiring clean and uninterrupted power.

Small Server Rooms Server Racks Workstations POS Systems ATM Machines Banking Equipment Network Equipment Telecom Systems Office Equipment IT Infrastructure Production Equipment Commercial Facilities
Technical Specifications

Delta N Series 6 kVA & 10 kVA Online UPS Specifications

Core technical specifications for the Delta Amplon N-6K and N-10K single-phase online UPS models.

Models N-6K and N-10K
Power Rating 6 kVA / 6 kW and 10 kVA / 10 kW
UPS Technology True online double-conversion topology
Phase Configuration Single-phase online UPS
Input Voltage 200 / 208 / 220 / 230 / 240 Vac
Input Voltage Range 100–280 Vac with load de-rating depending on selected nominal voltage
Input Frequency 40–70 Hz
Input Power Factor > 0.99 at full load
Input Current THD < 3%
Output Power Factor 1.0 / Unity power factor
Output Voltage 200 / 208 / 220 / 230 / 240 Vac
Output Frequency 50 / 60 Hz ±0.05 Hz
Output Voltage THD < 2% with linear load
Overload Capability Below 105% continuous; 105–125% for 2 minutes; 125–150% for 30 seconds
Crest Factor 3:1
AC-AC Efficiency Up to 95%
ECO Mode Efficiency Up to 98%
Battery Voltage 192–264 Vdc adjustable
Charge Current 1.5–8 A selectable
Parallel Operation Up to 4 compatible UPS units
Redundancy N+X parallel redundancy support
Display LCD display with LED status indicators
Communication REPO ×1, RS-232 ×1, USB ×1, Parallel Port ×2 and Smart Slot ×1
Audible Noise < 50 dBA
Dimensions 190 × 390 × 325 mm (W × D × H)
N-6K Weight Approximately 10.1 kg
N-10K Weight Approximately 12.7 kg
Operating Altitude Up to 1000 metres without de-rating
Operating Temperature 0–40°C at 100% load; higher-temperature operation subject to de-rating
Relative Humidity 5–95% non-condensing
MPower Support

From UPS Selection to Installation & AMC

Correct UPS selection requires more than choosing a kVA rating. MPower can assist with load assessment, battery sizing, installation and ongoing support.

01

Load Assessment

Evaluation of connected equipment, actual load, power factor, criticality and future expansion.

02

UPS Selection

Recommendation of the appropriate N-6K or N-10K UPS according to your application requirements.

03

Battery Sizing

Battery-bank sizing based on required backup duration, connected load and operating conditions.

04

Installation & Service

Support for supply, installation, commissioning, preventive maintenance, battery replacement and UPS AMC requirements.

Frequently Asked Questions

Questions About 6 kVA & 10 kVA Online UPS Systems

What is a 10 kVA Online UPS used for?

A 10 kVA Online UPS is commonly used to protect small server rooms, networking infrastructure, workstations, ATMs, POS systems, office equipment, production equipment and other sensitive business loads requiring uninterrupted conditioned power.

What is the difference between the 6 kVA and 10 kVA models?

The N-6K provides a rated capacity of 6 kVA / 6 kW, while the N-10K provides 10 kVA / 10 kW. The suitable model depends primarily on your connected load, future expansion and required operating margin.

Is the Delta N Series a true online UPS?

Yes. The Amplon N Series uses true online double-conversion topology to continuously condition power and provide zero-transfer-time protection to connected equipment.

Does the 10 kVA UPS provide 10 kW output?

Yes. The N-10K has a unity output power factor and is rated at 10 kVA / 10 kW, allowing the full rated capacity to be used for compatible connected loads.

Can multiple N Series UPS units run in parallel?

Yes. Compatible N Series units support parallel operation of up to four UPS systems for capacity expansion and N+X redundancy.

Is the N Series UPS compatible with generators?

Yes. Generator compatibility helps the UPS provide dependable power protection during prolonged utility outages when the facility is operating on generator power.

How much battery backup will a 10 kVA UPS provide?

Backup duration depends on the actual connected load, battery capacity, battery configuration, battery condition and required runtime. MPower can size the battery bank according to your required backup duration.

What is the price of a 10 kVA Online UPS?

The final 10 kVA Online UPS price depends on the UPS configuration, battery-bank capacity, required backup time, accessories, installation requirements and project location. Request a quotation for an accurately sized solution.

Get a Quote for Delta 6 kVA or 10 kVA Online UPS

Share your connected load, application and required backup time. MPower will help recommend the suitable Delta Amplon N Series UPS and battery configuration for your requirement.

Get Quote

Get Quote

Download Brochure

    Download Brochure

      Download Brochure

        Download Brochure

          Download Brochure

            Download Brochure

              Download Brochure

                Download Brochure

                  Download Brochure

                    Download Brochure

                      Download Brochure

                        Download Brochure

                          Download Brochure

                            Download Brochure

                              Download Brochure

                                Download Brochure

                                  Download Brochure

                                    Download Brochure

                                      Download Brochure

                                        Download Brochure

                                          Download Brochure

                                            Download Brochure